Rockwell Automation 1203-USB Converter User Manual
Page 63
Converter Parameters
B-3
PowerFlex 1203-USB Converter User Manual
Publication DRIVES-UM001D-EN-P
03
[Clear DF1 Counts]
No action if set to ‘0’ (Ready). Resets the DF1
statistical
Parameter 04 - [DF1 Packets Sent] and
Parameter 05 - [DF1 Packets Rcvd] to 0 (zero) if set
to ‘1’ (Clear Counts). This parameter is a command. It
will be reset to ‘0’ (Ready) after the command has been
performed.
Default:
0 = Ready
Values:
0 = Ready
1 = Clear Counts
Type:
Read/Write
Reset Required: No
04
[DF1 Packets Sent]
Displays the number of DF1 packets sent by the
converter. The value of this parameter is normally
approximately equal to the value of
Parameter 05 -
[DF1 Packets Rcvd].
Default:
0
Minimum:
0
Maximum:
65535
Type:
Read Only
05
[DF1 Packets Rcvd]
Displays the number of DF1 packets received by the
converter. The value of this parameter is normally
approximately equal to the value of
Parameter 04 -
[DF1 Packets Sent].
Default:
0
Minimum:
0
Maximum:
65535
Type:
Read Only
06
[RTU DSI Addr Cfg]
Sets the node address of the converter for use with the
converter operating mode set with
Parameter 01 -
[Adapter Cfg]. In Auto, Master, or Slave mode, the
converter node address can be any valid value. In RTU
Master or RTU Master Passthru mode, the converter
node address must match the address of any drive on
the network. Each network drive address must be
unique. In any case, the RTU DSI address is a decimal
value.
Default:
1
Minimum:
1
Maximum:
247
Type:
Read/Write
Reset Required: Yes
07
[RTU DSI Addr Act]
Displays the node address of the drive that the
converter is communicating with when the converter is
set to RTU Master or RTU Passthru mode using
Parameter 01 - [Adapter Cfg].
Default:
1
Minimum:
1
Maximum:
247
Type:
Read Only
08
[Adapter Type]
Displays the present operating mode for the converter.
Default:
0 = Master
Values:
0 = Master
1 = Slave
2 = RTU Master
3 = RTU Passthru
Type:
Read Only
No. Name and Description
Details