Parameters – dsi drives – Rockwell Automation 1203-USB Converter User Manual
Page 62
B-2
Converter Parameters
PowerFlex 1203-USB Converter User Manual
Publication DRIVES-UM001D-EN-P
Parameters – DSI Drives
05
[DF1 Packets Rcvd]
Displays the number of DF1 packets received by the
converter. The value of this parameter is normally
approximately equal to the value of
Parameter 04 -
[DF1 Packets Sent].
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read Only
06
[Interface Mode]
Sets the interface operating mode.
Auto:
The converter will automatically run DPI if
connected to a DPI drive, or SCANport if
connected to a SCANport legacy drive.
SCANport: The converter will perform SCANport
services only.
Set this parameter to ‘0’ (Auto, the default) unless you
are using DriveTools32 software, version 2.xx, and you
are connected to a DPI drive. In this case, use the ‘1’
(SCANport) setting.
Default:
0 = Auto
Values:
0 = Auto
1 = SCANport
Type:
Read/Write
Reset Required: Yes
07
[DPI Data Rate]
Displays the data rate used by the DPI host drive. This
data rate is set in the drive, and the converter
autobauds to it.
Default:
0
Values:
0 = 125 kbps
1 = 500 kbps
Type:
Read Only
08
[Ref/Fdbk Size]
Displays the size of the Reference/Feedback. The host
drive determines the size of the Reference/Feedback.
The converter automatically uses the correct size.
Default:
0 = 16-bit
Value:
0 = 16-bit
1 = 32-bit
Type:
Read Only
09
[Datalink Size]
Displays the size of each Datalink word. The host drive
determines the size of Datalinks.
Default:
0 = 16-bit
Values:
0 = 16-bit
1 = 32-bit
Type:
Read Only
No. Name and Description
Details
No. Name and Description
Details
01
[Adapter Cfg]
Sets the operation of the converter on DSI. Leave at
the ‘0’ (Auto) default setting when used with software
tools point-to-point.
Default:
0 = Auto
Values:
0 = Auto
1 = Master
2 = Slave
3 = RTU Master
4 = RTU Passthru
Type:
Read/Write
Reset Required: Yes
02
[Reset Module]
No action if set to ‘0’ (Ready). Resets the converter if
set to ‘1’ (Reset Module). Restores the converter to its
factory default settings if set to ‘2’ (Set Defaults). This
parameter is a command. It will be reset to ‘0’ (Ready)
after the command has been performed.
Default:
0 = Ready
Values:
0 = Ready
1 = Reset Module
2 = Set Defaults
Type:
Read/Write
Reset Required: No
!
ATTENTION: Risk of injury or equipment damage exists. If the converter is
transmitting I/O that controls the drive (indicated by a steady green diamond
status indicator), the drive may fault when you remove or reset the converter.
Determine how your drive will respond before removing or resetting a connected
converter.