B-2

Converter Parameters

PowerFlex 1203-USB Converter User Manual

Publication DRIVES-UM001D-EN-P

Parameters – DSI Drives

05

[DF1 Packets Rcvd]
Displays the number of DF1 packets received by the

converter. The value of this parameter is normally

approximately equal to the value of

Parameter 04 -

[DF1 Packets Sent].

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read Only

06

[Interface Mode]
Sets the interface operating mode.
Auto:

The converter will automatically run DPI if

connected to a DPI drive, or SCANport if

connected to a SCANport legacy drive.

SCANport: The converter will perform SCANport

services only.

Set this parameter to ‘0’ (Auto, the default) unless you

are using DriveTools32 software, version 2.xx, and you

are connected to a DPI drive. In this case, use the ‘1’

(SCANport) setting.

Default:

0 = Auto

Values:

0 = Auto

1 = SCANport

Type:

Read/Write

Reset Required: Yes

07

[DPI Data Rate]
Displays the data rate used by the DPI host drive. This

data rate is set in the drive, and the converter

autobauds to it.

Default:

0

Values:

0 = 125 kbps

1 = 500 kbps

Type:

Read Only

08

[Ref/Fdbk Size]
Displays the size of the Reference/Feedback. The host

drive determines the size of the Reference/Feedback.

The converter automatically uses the correct size.

Default:

0 = 16-bit

Value:

0 = 16-bit

1 = 32-bit

Type:

Read Only

09

[Datalink Size]
Displays the size of each Datalink word. The host drive

determines the size of Datalinks.

Default:

0 = 16-bit

Values:

0 = 16-bit

1 = 32-bit

Type:

Read Only

No. Name and Description

Details

No. Name and Description

Details

01

[Adapter Cfg]
Sets the operation of the converter on DSI. Leave at

the ‘0’ (Auto) default setting when used with software

tools point-to-point.

Default:

0 = Auto

Values:

0 = Auto

1 = Master

2 = Slave

3 = RTU Master

4 = RTU Passthru

Type:

Read/Write

Reset Required: Yes

02

[Reset Module]
No action if set to ‘0’ (Ready). Resets the converter if

set to ‘1’ (Reset Module). Restores the converter to its

factory default settings if set to ‘2’ (Set Defaults). This

parameter is a command. It will be reset to ‘0’ (Ready)

after the command has been performed.

Default:

0 = Ready

Values:

0 = Ready

1 = Reset Module

2 = Set Defaults

Type:

Read/Write

Reset Required: No

!

ATTENTION: Risk of injury or equipment damage exists. If the converter is

transmitting I/O that controls the drive (indicated by a steady green diamond

status indicator), the drive may fault when you remove or reset the converter.

Determine how your drive will respond before removing or resetting a connected

converter.