Troubleshooting potential problems, No communication to the drive, Cannot communicate with a scanport-based drive – Rockwell Automation 1203-USB Converter User Manual
Page 58: Troubleshooting potential problems -10
![background image](/manuals/580876/58/background.png)
4-10
Troubleshooting
PowerFlex 1203-USB Converter User Manual
Publication DRIVES-UM001D-EN-P
4. To clear the DF1 counters, set converter Parameter 03 - [Clear DF1
Counts] to ‘1’ (Clear Counts).
5. Press Enter.
Troubleshooting Potential
Problems
This section provides information about common converter problems and
actions that can be taken to correct them.
Unable to Establish Connection Between the Computer and Converter
• If the 1203-USB converter status indicators are off, connect the converter
cables and apply power to the drive. The converter draws its power from
the drive.
• Configure RSLinx to use the correct virtual COM port and baud rate. See
for the virtual COM port. The only baud rate that works is
115200.
No Communication to the Drive
• When connected to DPI-based drives, verify that converter
Parameter 06 - [Interface Mode] is set to ‘0’ (Auto).
• When connected to DSI-based drives, verify that converter
Parameter 01 - [Adapter Cfg] is set to ‘0’ (Auto).
Cannot Communicate with a SCANport-based Drive
Connected Components Workbench software does not support
SCANport-based devices. Use DriveExplorer or DriveExecutive software
for these devices.