Analog data format – Rockwell Automation 1794-XXXX FLEX I/O High-Density Analog Modules User Manual
Page 82
![background image](/manuals/580693/82/background.png)
Publication 1794-UM062A-EN-P - September 2012
74
Module Programming
The two’s complement of 0 is not found, since no first ”1” is ever encountered in
the number. The two’s complement of 0 then is still 0.
Analog Data Format
The data returned from the analog-to-digital converter in the module is 12-bit
resolute. This value is left-justified into a 16-bit field, reserving the most
significant bit for a sign bit.
Current and Voltage Mode Values
Current (mA) 4…20 mA Mode 0…20 mA Mode Voltage (V)
± 10V Mode
0…10V Mode
Input
Output
-10.50
8000
8000
0.00
0000
-10.00
8620
8618
1.00
0618
-9.00
9250
9248
2.00
0C30
-8.00
9E80
9E78
3.00
1248
-7.00
AAB0
AAA8
4.00
0000
1860
-6.00
B6E0
B6D8
5.00
0787
1E78
-5.00
C310
C310
6.00
0F0F
2490
-4.00
CF40
CF40
7.00
1696
2AA8
-3.00
DB70
DB70
8.00
1E1E
30C0
-2.00
E7A0
E7A0
9.00
25A5
36D8
-1.00
F3D0
F3D0
10.00
2D2D
3CF0
0.00
0000
0000
0000
11.00
34B4
4310
1.00
0C30
0C30
0C30
12.00
3C3C
4928
2.00
1860
1860
1860
13.00
43C3
4F40
3.00
2490
2490
2490
14.00
4B4B
5558
4.00
30C0
30C0
30C0
15.00
52D2
5B70
5.00
3CF0
3CF0
3CF0
14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
11 10 09 08 07 06 05 04 03 02 01 00
S
S
14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
10 09 08 07 06 05 04 03 02 01 00
S
S
14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
11 10 09 08 07 06 05 04 03 02 01 00
0*
A/D unipolar data
A/D bipolar data
D / A d a t a
Output
Input
A n a l o g v a l u e
A n a l o g v a l u e
A n a l o g v a l u e
*
= A l w a y s p o s i t i v e
xxxxx