Environmental specifications – Rockwell Automation 1794-XXXX FLEX I/O High-Density Analog Modules User Manual
Page 47
![background image](/manuals/580693/47/background.png)
Publication 1794-UM062A-EN-P - September 2012
Specifications 39
Environmental Specifications
The following are the environmental specifications common to all the FLEX I/O
analog modules in this publication.
Environmental Specifications
Specification
Description
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…55 °C (32…131 °F)
-20…60 °C (-40…185 °F) – For 1794-IE12, 1794-OE12 and 1794-IE8XOE4 only
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
–40…85 °C (–40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 H
Shock, operating
IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30 g
Shock, nonoperating
IEC60068-2-27 (Test Ea, Unpackaged shock):
Nonoperating 50 g
Emissions
CISPR 11:
Group 1, Class A
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
4 kV contact discharges – For 1794-IE8, 1794-OE4, 1794-IE4XOE2 and 1794-IE4XOE2XT only
8 kV air discharges
Radiated RF immunity
1794-IE12, 1794-OE12, 1794-IE8XOE4
IEC 61000-4-3:
10 V/m with 1 kHz sine-wave 80% AM from 30…2000 MHz
10 V/m with 200 Hz 50% pulse 100% AM at 900 MHz
10 V/m with 200 Hz 50% pulse 100% AM at 1890 MHz
3 V/m with 1 kHz sine-wave 80% AM from 2…2.7 GHz
1794-IE8, 1794-OE4, 1794-IE4XOE2 and 1794-IE4XOE2XT
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz
EFT/B immunity
IEC 61000-4-4:
±2 kV at 5 kHz on power ports – For 1794-IE12, 1794-OE12, 1794-IE8XOE4 only
±2 kV at 5 kHz on signal ports