beautypg.com

Connecting readers to slc 5/03 controller – Rockwell Automation 2755-SNx Adaptascan Bar Code Readers User Manual

Page 110

background image

7–4

Communicating with an SLC on a DH-485 Network

Publication 2755-6.8

Connecting Readers to SLC 5/03 Controller

You must use a link coupler if the distance between the reader and
the SLC is greater than 15.2 meters (50 feet). The reader can
connect directly to another RS-485/RS-422 device. Point-to-point
and network connections are the same.

The end devices on the DH-485 network must be terminated. The
wiring base of the AdaptaScan Reader provides a termination switch.

Termination Switch

Ground

Shield

RS-485/422

RS-485/422

RS-422

RS-422

Term
A
B
Com
Shield
Chassis Gnd

SLC 5/03 Processor

Computer

1747-PIC

1747-AIC Module

2755-ASN AdaptaScan Software
SLC 500 Advanced Programming Software

AdaptaScan Wiring Base

RS-422/RS-485 Terminal

AdaptaScan Wiring Base

RS-422/RS-485 Terminal

Power

Supply