Configure adapter summary, Adapter mode, Important – Rockwell Automation 1756-RIO ControlLogix Remote I/O Communication Interface Module User Manual User Manual
Page 62

62
Publication 1756-UM534B-EN-P - November 2010
Chapter 3 Configure Adapter Mode
Adapter Mode
Configure Adapter
Summary
The following list summarizes the steps to configure the 1756-RIO module in
adapter mode.
1. Set the baud rate.
2. Autoconfigure online racks on the network. (Make sure the controller is
set to Program Mode.)
3. Set the communication path.
4. Manually add any additional racks that are not online.
5. Manually add and configure block transfer modules.
6. Map/Automap the data.
RIO Scanner
(reads inputs and
writes outputs to
scanned racks)
PLC-3, PLC-5, SLC, Etc.
C
ontr
olL
og
ix
1756-RIO in A
dapt
er
M
onit
or M
ode
1771 I/O Rack
1747 I/O Rack
Rack 1
Rack 2
Rack 3
1771 I/O Rack
Rack 4
RIO Scanner
(reads inputs and
writes ouputs to
scanned racks)
PLC-3, PLC-5, SLC, Etc.
1771 I/O Rack
1771 I/O Rack
1747 I/O Rack
Rack 1
1756-RIO
In A
dapt
er
M
ode
C
ontr
olL
og
ix
Rack 4
Rack 3
Rack 2
Two-way
communication
between the RIO
scanner and the
1756-RIO module
in adapter mode.
1756-RIO Module as an Active Rack
1756-RIO Module as a Monitored Rack
One-way
communication
between the Remote I/
O network and the
ControlLogix controller.
The RIO scanner
controls the I/O and
the ControlLogix
controller via the 1756-
RIO module in adapter
monitors all I/O data.
In monitor mode, it
monitors the I/O and
brings all input and
output data into the
ControLogix controller.
44828
44829
Universal Remote I/O Network
IMPORTANT
Configuring the 1756-RIO module as an adapter enables the RIO
module to emulate a 1771-ASB module. This allows a path for
peer-to-peer data to be exchanged between the scanner
controller and the ControlLogix owner of the RIO module over
the Remote I/O network. The adapter mode functionality does
not allow the scanner controller to directly control any 1756-I/O
in the chassis with the RIO module.