Monitor Remote I/O Chapter 5
Global Diagnostic Counters
The global diagnostic counters provide information about the operation of the
entire Remote I/O network.
The following table lists the global diagnostic counters’ descriptions.
Scanner Mode Global Diagnostic Counters
Counter
Description
Tx
This counter increments each time the 1756-RIO module transmits a packet.
RxGood
This counter increments when the 1756-RIO module receives a good packet.
RxTout
This counter increments when the 1756-RIO module sends a packet but does not receive a reply.
RxBadCRC
This counter increments when the 1756-RIO module receives a packet with a bad Cyclic Redundancy Check (CRC). Check
cabling and termination on the Remote I/O network.
RxNoise
This counter increments when the 1756-RIO module hears a carrier without receiving a packet. Check cabling and
termination on the Remote I/O network.
RxAbort
This counter increments when the 1756-RIO module receives an opening flag, then the packet ends without a closing
flag.
PrtclErr
This counter increments when the 1756-RIO module receives a packet that makes no sense in terms of the protocol.
UpdAvg
Average update time for all configured racks. This is the average of the previous 64 updates.
UpdMin
Minimum update time for all configured racks.
UpdMax
Maximum update time for all configured racks.