Chapter 5 Monitor Remote I/O
Block Transfer Read Diagnostics
The following table lists the diagnostics for block transfer reads.
Scanner Mode Block Transfer Read Diagnostics
Counter
Description
State
Config/active/inactive.
Type
Module type from the module template.
BTR Len
Block transfer read length.
Req Update Time
Requested update time in the module configuration, in ms.
Avg Update Time
Average update time for this block transfer read, in ms. This is the average of the previous eight updates.
Min Update Time
Minimum update time for this block transfer read, in ms.
Max Update Time
Maximum update time for this block transfer read, in ms.
Update Count
Running count of updates for this block transfer read.
Ignored Reqs
Running count of update requests ignored by the block transfer module.
Prot Errors
Running count of protocol errors for this block transfer read. If this counter is incrementing, the module isn’t
responding correctly.
Request Count
Count of the number of times on successive scans this block transfer was requested. If this number is
consistently greater than 1, increase the requested update time - the module cannot respond quickly enough at
the current requested time. The counter applies to the BTR and BTW for this module.