24 Blow-molding Module
Publication 1746-IN014B-EN-P - January 2001
Minimizing interference from radiated electrical noise:
•
Isolate signal wiring (such as LVDT input cables) from power lines and
sources of electrical noise (such as motors and proportional amplifiers).
•
Use shielded twisted pairs for all input and output connections.
•
Make cables and unshielded leads as short as possible.
•
Connect the shields of LVDT input cables and drive-output cables to earth
ground at the I/O chassis at the nearest chassis mounting bolt.
•
Ground cable shields at one end only.
•
Connect all of the following to earth ground:
– power supply cable shields
– LDT flange, frame, and machine
– I/O chassis
– a/c ground
•
Place the SLC processor and I/O chassis in a suitable enclosure.
•
About the Interface Module Terminal Block (cat. no. 1492-IFM40F)
We recommend that you use this device for connections to the module.
The associated cable connects the device to the module. Cables are available in
standard sizes as indicated by part number 1492-CABLExxxH where xxx indicates
cable length in meters:
Publication 1492-5.1 describes the IFM terminal block and cables. For information
on the entire line of Interface Modules and associated cables for wiring analog
systems, see publication 1492-2.15.