Flow measurement parameters – Rockwell Automation 1758-RTU202 DataSite Hardware User Manual User Manual
Page 66
![background image](/manuals/579362/66/background.png)
Publication 1758-UM001D-EN-P - June 2011
66 Specifications
Flow Measurement
Parameters
The flow measurement specifications apply to 1758-FLO DataSite controllers
only.
Flow Measurement Specifications (for 1758-FLO controllers only)
Attribute
Value
Meter channels
1…8 channels
Meter algorithm
AGA3/AGA7 are optional. The default is AGA3.
Compressibility factor calculation using AGA8.
Clock
Accuracy 0.08s/24h, support calibration
Operation
With the software tools, DS FloConfig and DS DNP3.
Secuity of the system
With special license code for flow computer controller and
password for parameters modification.
Data acquisition cycle
Acquisition cycle of AI-channel is 100 ms. For DI and PI
channels, it is 10 ms.
Flow calculation cycle
1 s
Base conditions
User can change the base conditions.
Compressibility factor
calculation
Three methods of AGA8 optional: Gas analysis, HV-GR-CO2,
GR-CO2-N2
Pressure tap location
Support flange upstream and downstream tap pressure
Transient flow calculation
Supports transient volume hour flow rate calculation in base
conditions and flowing conditions. Supports mass flow rate
calculation. Supports low or zero flow cutoff.
Flow transaction records
Store the hourly and daily historical transaction records
during 35 days. If parameters are changed, a new hourly and
daily record will be logged.
Event records
700 event records
Alarm records
300 alarm records
Accumulative total
Long integer
Overall accuracy
±0.2% F.S.