Recommended surge suppressors, Power source requirements – Rockwell Automation 1758-RTU202 DataSite Hardware User Manual User Manual
Page 28
![background image](/manuals/579362/28/background.png)
Publication 1758-UM001D-EN-P - June 2011
28 Wiring the Controller
Recommended Surge Suppressors
Use the Allen-Bradley surge suppressors shown in the following table for use
with relays, contactors, and starters.
Power Source
Requirements
Recommended Surge Suppressors
Device
Coil Voltage
Suppressor Catalog
Number
Bulletin 509 Motor Starter
Bulletin 509 Motor Starter
120V AC
240V AC
599-K04
(1)
599-KA04
(1)
(1)
Varistor – Not recommended for use on relay outputs.
Bulletin 100 Contactor
Bulletin 100 Contactor
120V AC
240V AC
199-FSMA1
(2)
199-FSMA2
(2)
(2)
RC Type – Do not use with Triac outputs.
Bulletin 709 Motor Starter
120V AC
1401-N10
(2)
Bulletin 700 Type R, RM Relays
AC coil
None Required
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
12V DC
12V DC
199-FSMA9
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
24V DC
24V DC
199-FSMA9
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
48V DC
48V DC
199-FSMA9
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
115-125V DC
115-125V DC
199-FSMA10
Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay
230-250V DC
230-250V DC
199-FSMA11
Bulletin 700 Type N, P, or PK Relay
150V max, AC or DC
700-N24
(2)
Miscellaneous electromagnetic
devices limited to 35 sealed VA
150V max, AC or DC
700-N24
(2)
ATTENTION
The DataSite controllers (catalog numbers 1758-FLO301,
1758-FLO302, 1758-RTU201, 1758-RTU202) must be powered
by a National Electrical Code (NEC) or Canadian Electrical Code
(CEC) Class 2 power source when used in locations covered by
Underwriters Laboratories.
In locations governed by International Electrotechnical
Commission (IEC) or EN standards, a Safety Extra Low Voltage
(SELV) power source must be used.