48 Operating the Controller
Sleep Mode
Sleep mode is available on 1758-RTU controllers only. 1758-FLO controllers
do not provide Sleep mode due to requirements for periodic execution of the
AGA gas flow calculations.
DataSite controllers are capable of extremely low power operation when in
Sleep mode. In Sleep mode, the following will occur:
• All programs stop executing.
• The power supply of 3.3V for circuit is shut off.
• The real-time clock and timer continue to function.
• 12V DC power is not affected.
DataSite controllers can switch to Sleep mode under control of the application
program. If one of the following conditions occurs, the controller will be
switched out of Sleep mode to return to normal operation.
• A real-time clock alarm, as defined by an application program, is
triggered.
• A high voltage level signal is applied to the WakeUp input.
LED Indicators
Indicator
State
Description
PWR
Green
Power is applied. This indicator is not affected by
LED power control settings.
RUN
Green
Normal operation. This indicator is not affected by
LED power control settings.
STAT
Flasing red
DataSite application running
ERR
Yellow
Error detected
DI0…DI7
Green
Corresponding digital input is on
DO0…DO3
Green
Corresponding digital output is on
PI0…PI2
Green
Corresponding pulse input voltage is more than 8V
TX0
Flashing red
Transmitting data through HART port
RX0
Flashing green
Receiving data through HART port
TX1
Flashing red
Transmitting data through serial port 1
RX1
Flashing green
Receiving data through serial port 1
TX2
Flashing red
Transmitting data through serial port 2
PWR STAT DO0 DO2
DI0
DI2
DI4
DI6
PI0
PI2
TX0 TX1
TX2 10\100M
RUN ERR
DO1 DO3
DI1
DI3
DI5
DI7
PI1
LINK RX0 RX1
RX2 F\H