4-18 Programming Overview

Figure 4.5 Data Flow Between the SLC processor and Port DH485 of the Module

In addition, the commands in the following table provide status of the
data transfer between the SLC processor and port DH485 of the
module.

For more information regarding the use of these commands, refer to
the BASIC Language Reference Manual, publication 1747-RM001.

CALL 91

Transfers words 0...39 of the module output buffer to a remote DH485 data
file.

CALL 92

Transfers the data from a remote DH485 interface file to words 0...39 of the
module input buffer.

CALL 93

Transfers words 0...39 of the module output buffer to a remote DH485
interface file.

CALL 118

Allows unsolicited writes from a remote SLC or PLC node.

Command

Purpose

SLC Processor

256 bytes

256 bytes

PORT DH485

PRINT

CALL 28

CALL 27

CALL 118

INPUT

CALL 14/15

CALL 24/25

CALL 90/92
CALL 84

CALL 91/93

CALL 85

256 bytes
256 bytes

COMMON

INTERFACE INPUT

FILE

COMMON

INTERFACE

OUTPUT FILE

ASCII OUTPUT

QUEUE

BASIC INPUT

BUFFER

BASIC

OUTPUT

BUFFER

ASCII INPUT

QUEUE

Command Purpose

MODE

Sets the port parameters of PRT1, PRT2, and DH485.

CALL 86

Checks the remote write status of the DH485 common interface file.

CALL 87

Checks the remote read status of the DH485 common interface file.