Rockwell Automation 1746-NI8 SLC 500 Analog Input Modules User Manual User Manual

Page 70

background image

8–5

Application Examples

Publication 1746Ć6.8 - April 1997

Channel Configuration

Configuration setup for current transducers:

channels 0, 1, and 2

4–20 mA input type

engineering units data format

zero data word in the event of an open circuit

10 Hz input filter to reject high frequency noise and provide
60 Hz line noise rejection

Configuration setup for pressure transducer:

channel 3

4–20 mA input type

engineering units data format

zero data word in the event of an open circuit

10 Hz input filter to reject high frequency noise and provide
60 Hz line noise rejection

Configuration setup for level sensor:

channel 4

0–10V dc input type

engineering units data format

zero data word in the event of an open circuit

10 Hz input filter to reject high frequency noise and provide
60 Hz line noise rejection