beautypg.com

Class 1 and class 3 interface, Module addressing, Class 1 and class 3 interface module addressing – Rockwell Automation 1746-NI8 SLC 500 Analog Input Modules User Manual User Manual

Page 33

background image

4–2

Preliminary Operating Considerations

Publication 1746Ć6.8 - April 1997

The 1746-NI8 analog input module has multiclass interface
capabilities. Class 1 is the standard configuration. The module can
be configured through the user program for Class 3 which enables
user-defined data scaling and monitoring of channel status words.

Configuration

Class 1

Class 3

Compatible SLC

Processors

SLC 500 fixed, SLC 5/01, SLC 5/02,

SLC 5/03, and SLC 5/04

SLC 5/02, SLC 5/03, and SLC 5/04

Compatible

Chassis

local chassis or remote chassis with a

1747ĆASB module

local chassis

Input and

Output Images

output image:

8 channel configuration words

input image:

8 channel data words

output image:

8 channel configuration words and 4 limit ranges

for userĆdefined scaling data format

input image:

8 channel data words and 8 channel status words

Default

Class 1 is the default on powerĆup

Class 3 is programmable by user

The following memory maps show you how the input and output
input image tables are defined for Class 1 and Class 3.

Class 1 Memory Map

Channel 0 Configuration Word
Channel 1 Configuration Word
Channel 2 Configuration Word
Channel 3 Configuration Word

Channel 0 Data Word
Channel 1 Data Word
Channel 2 Data Word
Channel 3 Data Word
Channel 4 Data Word
Channel 5 Data Word
Channel 6 Data Word
Channel 7 Data Word

Output Image

8 Words

Input Image

8 Words

Output Image

Input Image

Output

Scan

Input

Scan

Output Image

Input Image

Slot e

Slot e

SLC 5/0X

Data Files

Analog Input

Module

Image Table

Bit 15

Bit 0

Bit 15

Bit 0

Word 0
Word 1
Word 2
Word 3

Word 7

.
.
.

.
.
.

Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7

Address

Address

O:e.0
O:e.1
O:e.2
O:e.3

O:e.7

I:e.0
I:e.1
I:e.2
I:e.3
I:e.4
I:e.5
I:e.6
I:e.7

(Class 1)

Channel 4 Configuration Word
Channel 5 Configuration Word
Channel 6 Configuration Word
Channel 7 Configuration Word

Class 1 and Class 3

Interface

Module Addressing