5–12
Channel Configuration, Data, and Status
Publication 1746Ć6.8 - April 1997
Channel 0-7 Status Word (I:e.8 through I:e.15) - Bit Definitions
Bit(s)
Define
These bit settings
Indicate this
Bit(s)
Define
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Indicate this
0
0
0
"
10 V dc
0
0
1
1-5V dc
0
1
0
0-5V dc
0 2
Input Type
0
1
1
0-10V dc
0-2
Input Type
1
0
0
0-20 mA
1
0
1
4-20 mA
1
1
0
"
20 mA
1
1
1
0-1 mA
0
0
0
Engineering Units
0
0
1
ScaledĆforĆPID
0
1
0
Proportional Counts
3-5
Data Format
0
1
1
1746ĆNI4 Data Format
3-5
Data Format
1
0
0
User Defined (Class 3)
1
0
1
User Defined (Class 3)
ЙЙЙ
ЙЙЙ
ЙЙ
ЙЙ
ЙЙ
ЙЙ
ЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙ
Illegal (configuration error)
ЙЙЙ
ЙЙ
ЙЙ
ЙЙЙЙЙЙЙЙ
Illegal (configuration error)
0
0
Zero
6 and 7
Open Circuit
0
1
Upscale
6 and 7
Open Circuit
1
0
Downscale
ЙЙ
ЙЙ
ЙЙ
ЙЙ
ЙЙЙЙЙЙЙЙ
ЙЙЙЙЙЙЙЙ
Illegal (configuration error)
0
0
0
No Filter
0
0
1
75 Hz
0
1
0
50 Hz
8 10
Filter
0
1
1
20 Hz
8-10
Filter
Frequency
1
0
0
10 Hz
q
y
1
0
1
5 Hz
1
1
0
2 Hz
1
1
1
1 Hz
11
Channel
0
Channel Disabled
11
Channel
Status
1
Channel Enabled
12
Open Circuit
0
No Error
12
Open Circuit
Error
1
Open Circuit Detected
13
OverĆRange
0
No error
13
Over Range
Error
1
OverĆRange Condition
14
UnderĆRange
0
No Error
14
Under Range
Error
1
UnderĆRange Condition
15
Configuration
0
No Error
15
Configuration
Error
1
Configuration Error
Important: If the channel for which you are seeking status is
disabled (bit O:e.x/11 = 0), all bit fields are cleared.
The status word for any disabled channel is always
0000 0000 0000 0000 regardless of any previous setting
that may have been made to the configuration word.