Rockwell Automation 1734-ADNX POINT I/O DeviceNet Adpater User Manual User Manual
Page 93
Publication 1734-UM002C-EN-P - July 2003
1734-ADNX Quick Start B-13
Notice that parameters 9, 10, 11 and 12 are still at their default of
2 bytes. These values will be filled out for you when this action
is complete.
4. Make sure All is selected then click the icon to download
parameters to the device (this triggers the Auto Start Mode).
5. Click the Monitor icon and notice:
• Parameter 6 has gone back to "Do Nothing". The Auto Start
has begun and will not repeat unless you trigger it again later.
• Parameter 8 indicates you are in Auto Start Mode. Give the
system at least a minute or two to complete the configuration
you requested then go to the next step.
6. Wait for parameter 8 to return to idle. Then click the Monitor
icon to end Monitoring. Notice the following:
• Parameter 1 has been filled in for you. There are two POINT
I/O modules in the backplane, causing the default to change
from 31 to 2.
Download
parameters to
the device
Monitor
icon