beautypg.com

Rockwell Automation 1734-ADNX POINT I/O DeviceNet Adpater User Manual User Manual

Page 74

background image

Publication 1734-UM002C-EN-P - July 2003

6-2 Troubleshooting the 1734-ADN(X) Adapter

Use the table below to troubleshoot your adapter.

Indicator:

Indication:

Probable Cause:

Take This Action:

System Power

Off

Any of the following:

1. Not active
2. Field power is OFF
3. DC-DC converter

problem

1. Check adapter

configuration

2. Turn field power ON
3. Check DC-DC

converter

Green

Any of the following:

1. System power ON
2. DC-DC converter

active (5V)

None

Field Power

Off

Any of the following:

1. Not active
2. Field power is OFF

1. Check adapter

configuration

2. Turn field power ON

Green

Power ON, 24V present

None

Adapter Status

Off

No power applied to device Power the adapter

Green

Device operating normally

None

Flashing Green

Device needs to be
commissioned because
configuration is missing,
incomplete or incorrect

Check configuration and
recommission the adapter

Flashing Red

Recoverable fault

Make sure the adapter
does not need a FLASH
update

Red

Unrecoverable fault may
require device replacement

Replace the adapter

Flashing
Red/Green

Device is in self-test

Wait for self-test to finish

This manual is related to the following products: