1734-it2i isolated thermocouple input module d-11, 1734-vhsc 24v dc high speed counter module d-11 – Rockwell Automation 1734-ADNX POINT I/O DeviceNet Adpater User Manual User Manual
Page 125

Publication 1734-UM002C-EN-P - July 2003
Default Data Maps
D-11
1734-IT2I Isolated Thermocouple Input Module
Message size: 8 Bytes
1734-VHSC 24V dc High Speed Counter Module
Message size: 6 Bytes
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Produces (scanner Rx) Input Channel 0 - High Byte
Input Channel 0 - Low Byte
Input Channel 1 - High Byte
Input Channel 1 - Low Byte
Status Byte for Channel 1
Status Byte for Channel 0
OR
UR
HHA
L
LA
HA
LA
CM
CF
OR
UR
HHA
L
LA
HA
LA
CM
CF
OR
UR
Cold Junction Temperature
(Selectable: Channel 0, Channel 1, or Average of both Channel 0 and 1)
Consumes (scanner
Tx)
No consumed data
Where: CF = Channel Fault status; 0 = no error, 1 = fault
CM = Calibration Mode; 0 = normal, 1 = calibration mode
LA = Low Alarm; 0 = no error, 1 = fault
HA = High Alarm; 0 = no error, 1 = fault
LLA = Low/Low Alarm; 0 = no error, 1 = fault
HHA = High/High Alarm; 0 = no error, 1 = fault
UR = Underrange; 0 = no error, 1 = fault
OR = Overrange; 0 = no error, 1 = fault
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Produces (scanner Rx) Channel 0 value of present counter state (LSW)
Channel 0 value of present counter state (MSW)
PE
EF
NR
0
FS
FS
OS
OS
0
ZS
BS
AS
C1
C0
ZD
0
Where: PE = Programming error
EF = EEPROM fault status
NR = Not ready status bit
FS = Output fault status bit - bit 10 for output 0, bit 11 for output 1
OS = Output on/off status bit - bit 8 for output 0, bit 9 for output 1
ZS = Z input status
BS = B input status
AS = A input status
C = Stored data count
ZD = Zero frequency detected
LSW = Least significant word