beautypg.com

Module status and input data, Chapter – Rockwell Automation 1771-OFE/B Analog Output Module User Manual User Manual

Page 51

background image

Chapter

5

Publication 1771Ć6.5.30 - November 1998

Module Status and Input Data

In this chapter, you will read about:

For information on

See page

ReadingData from the Module . . . . . . . . .

5-1

Block transfer read (BTR) programming moves status and data from
the module to the processor’s data table in one I/O scan. The
processor user program initiates the request to transfer data from the
module to the processor.

The transferred words contain module status, channel status and
input data from the module. The maximum BTR data file length
required is five words.

Figure 5.1

Word Assignment for Block Transfer Read

Decimal Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Word 1

Channel 1 DAC Input Data

2

Channel 2 DAC Input Data

3

Channel 3 DAC Input Data

4

Channel 4 DAC Input Data

5

Not

used

I/O

Reset

Reserved

Data Valid

Important: The user program that uses the read block transfer must

make sure that Bits 06 and 07 (the write enable and read
enable request bits) of the MCB are not set
simultaneously.

What This Chapter

Contains

Reading Data from the

Module