Word 5 of the block transfer write is the module configuration word
(Figure 3.1). It contains information on:

data polarity

scaling polarity

data format

Figure 3.1

Configuration Block Transfer Write Word 5

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Word5

4

4

3

3

2

2

1

1

4

3

2

1

Data Format

Reserved

1 = Binary
0 = BCD

Maximum Scaling Value Polarity

1 = Negative
0 = Positive

Minimum Scaling Value Polarity

1 = Negative
0 = Positive

Data Sign Polarity

1 = Negative
0 = Positive

4 = Channel 4

3 = Channel 3

2 = Channel 2

1 = Channel 1

12883

Table 3.A

Bit/Word Descriptions for Configuration Block Transfer Write

Word 5

Word

Decimal Bit

(Octal Bit)

Description

00Ć03

Data polarity bits. When set (1), indicate negative data. When reset (0), indicate

positive data. Bit 00 corresponds to channel 1, bit 01 to channel 2, etc.

04

When set (1), indicates negative minimum scaling value for Channel 1. When

reset (0), indicates positive minimum scaling value for channel 1.

5

05

When set (1), indicates negative maximum scaling value for Channel 1. When

reset (0), indicates positive maximum scaling value for channel 1.

5

06

When set (1), indicates negative minimum scaling value for Channel 2. When

reset (0), indicates positive minimum scaling value for channel 2.

07

When set (1), indicates negative maximum scaling value for Channel 2. When

reset (0), indicates positive maximum scaling value for channel 2.

08 (10)

When set (1), indicates negative minimum scaling value for Channel 3. When

reset (0), indicates positive minimum scaling value for channel 3.

Configuration Word