beautypg.com

Ground the chassis and module – Rockwell Automation 1771-OFE/B Analog Output Module User Manual User Manual

Page 24

background image

2-10

Publication 1771Ć6.5.30 - November 1998

The module requires shielded cable for signal transmission to the
analog devices. Use Belden 8761 shielded cable, which consists of a
single insulated, twisted-pair of conductors, covered along their
entire length by a foil shield and encased in plastic. The shield
reduces the effect of induced noise at any point along the cable.

You must ground the shield at the chassis end only. We recommend
connecting each output cable’s shield to a properly grounded
common bus. Refer to “Industrial Automation Wiring and Grounding
Guidelines for Noise Immunity,” publication 1770-4.1, for additional
information.

Figure 2.6

Cable Grounding

Remove a length of cable

jacket from the Belden 8761

cable.

Pull the foil shield and bare

drain wire from the insulated

wires.

Bare drain

wire

Insulated

wires

Foil

shield

Twist the foil shield and drain

wire together to form a single

strand.

Attach a ground lug.

20104

Belden 8761 Cable

19480

Grounding Stud

1

Use the cup washer if crimpĆon lugs are not used.

Chassis Ground

Ground Lug

Ground Lug

1

Star

Washer

I/O Chassis

Side Plate

Nut and Captive

Washer

ExternalĆtooth

Washers

#10 ThreadĆforming screw

19923

Shield and Drain

twisted together

Shield and Drain

twisted together

SingleĆpoint Grounding

Extend shield to termination point.

Expose just enough cable to adequately terminate inner conductors.

Use heat shrink tubing or

other suitable insulation

where wire exits cable

jacket.

Nut

When you connect grounding conductors to the I/O chassis

grounding stud, place a star washer under the first lug, then

place a nut with captive lock washer on top of each ground lug.

Ground the Chassis and

Module