Product id number read, Plc block transfer instruction data, Message operation – Rockwell Automation 1336-GM1 Remote I/O Communications Module User Manual
Page 72
B–8
Supported Block Transfer Messages
Product ID Number Read
Product ID Number Read returns the product ID of the device to
which the Remote I/O module is connected.
PLC Block Transfer Instruction Data
PLC request instruction length: 3 words
Drive response instruction length: 4 words
Figure B.6
Message Structure
Message Operation
Product ID Number Read, through the drive response message
word 3, indicates the type of device the Remote I/O module is
connected to. This value is defined in the message response chart
shown above.
If an error has occurred, word 1 of the response returns a negative
value of –32512.
Header
Word 0
PLC Decimal Value
256
Header
Word 1
Header
Word 2
PLC Request
Header Word 0
Header Word 1
Data Word 2
Message Length
Message Length
PLC Decimal Value
256 — Message OK
–32512 — Message Error
0
Drive Response
3
0
4
Data
Word 3
Product ID Number
or Error Code
Product Code
(Hex)
Product Code
(Decimal)
Bulletin
Number
Product
0x02
2
1336S
1336 PLUS 0.5 – 10 HP
0x03
3
1336S
1336 PLUS 7.5 – 800 HP
0x07
7
1336F
1336 PLUS II
0x10
16
1336T
1336 FORCE w/PLC Adapter Board
0x11
17
2364F
2364 RGU DC Bus Regen Front End
0x12
18
1394
1394 Motion Drive
0x13
19
1557
1557 Medium Voltage AC Drive
0x14
20
193
SMP-3
0x15
21
150
SMC Dialog Plus
0x17
23
1305
1305 AC Drive
0x18
24
1397
1397 DC Drive
0x19
25
1336R
1336 Line Regeneration Package
0x20
32
1336T
1336 FORCE w/Standard Adapter Board
0x22
34
1336E
1336 IMPACT