Troubleshooting

FAULT LED

SCANport STS LED

Health LED

Rem I/O ACT LED

Rem I/O STS LED

Early versions of Remote I/O modules use amber LEDs instead of green.

The SCANport product should be powered to ensure a successful auto-configure.

LED Status

Cause

Corrective Action

Red (Steady)

• Unrecoverable Fault

• Replace the module.

Red (Blinking)

• Recoverable Fault

• If Health LED is steady, a DIP switch is set incorrectly,

there is a bad cable, or an RIO connection between the
controller and adapter has not been made.

• Verify that the module is configured correctly.

• Verify that the SCANport and Remote I/O cables are correctly

wired and securely connected.

• Configure or auto-configure the controller.

Off

• Normal Operation

• None

LED Status

Cause

Corrective Action

Green (Steady)

• Normal Operation

• None

Green (Blinking)

• If FAULT LED is also blinking, the connected device is

not compatible.

• Verify that the connected product is compatible. Refer to Chapter 1.

Off

• No SCANport Connection.

• Verify that the module is connected to the SCANport product.

• Verify that the SCANport product is powered.

• Cycle power to the module.

LED Status

Cause

Corrective Action

Green (Steady)

• Normal Operation

• If FAULT LED is steady, a DIP switch is set incorrectly,

there is a bad cable, or an RIO connection between
the controller and adapter has not been made.

• None

• Verify that the module is correctly configured.

• Verify that SCANport and Remote I/O cables are correctly wired and

securely connected.

• Configure or auto-configure the controller.

Off

• Internal module fault

• Cycle power.

LED Status

Cause

Corrective Action

Green (Steady)

• Normal Operation

• None

Off

• No data is being received from the controller.

• Verify that Remote I/O is online.

• Verify that the controller is in run mode.

• Verify that rack addressing is set correctly.

• Verify that the module is connected to the controller.

LED Status

Cause

Corrective Action

Green (Steady)

• Normal Operation

• None

Green (Blinking)

• Controller is in reset, program, or test mode.

• Controller has more rack space allocated than is used.

• Return the controller to run mode.

• Configure or auto-configure the controller.

Off

• Module is not communicating with the controller.

• Module is not connected to the product.

• Verify that the module is connected to the controller.

• Verify that the controller is configured to recognize the module.

• Verify that the module is connected to the SCANport product.