beautypg.com

Rockwell Automation 1336-GM1 Remote I/O Communications Module User Manual

Page 45

background image

Creating Ladder Logic Programs

4–7

Logic Status Bits

The Logic Status bits for the 1336 PLUS drive that we use in our
example are as follows:

The 1305 drives, 1336 PLUS II drives, and 1336 Spider drives use the
same Logic Command and Logic Status data. For other drives, refer
to their user manuals.

Logic Status Bits

Function

Description

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

X

Enabled

1=Enabled, 0=Not Enabled

X

Running

1=Running, 0=Not Running

X

Command
Direction

1=Forward, 0=Reverse

X

Rotating Direction

1=Forward, 0=Reverse

X

Acceleration

1=Accelerating, 0=Not

X

Deceleration

1=Decelerating, 0=Not

X

Warning

1=Warning Present, 0=Not

X

Fault

1=Faulted, 0=Not Faulted

X

At Speed

1=At Speed, 0=Not At Speed

X

X

X

Local

000=Terminal I/O has Local

001=Port 1 has Local

010=Port 2 has Local

011=Port 3 has Local

100=Port 4 has Local

101=Port 5 has Local

110=Port 6 has Local

111=Multiplexed Control

X

X

X

X

Reference Source

0000=External Reference 1

0001 – 0111=Presets 1 – 7

1000=External Reference 2

1001 – 1110=Port 1 – 6 Direction

1111=Jog