Factory-default settings -3 quick configuration -3, Factory-default settings, Quick configuration – Rockwell Automation 1336-GM1 Remote I/O Communications Module User Manual
Page 19

Configuring the Module
2–3
Factory-Default Settings
The module is shipped with the following settings:
Quick Configuration
For detailed switch information, refer to pages 2–4 through 2–13.
Feature
Switch(es) Default Setting
Block Transfer
3.1
Enabled
Logic Command/Status
3.2
Enabled
Reference/Feedback
3.3
Enabled
Datalinks
3.4 – 3.7
Datalinks A and B are Enabled
Datalinks C and D are Disabled
Truncate Last Datalink
3.8
Disabled
Starting Group
2.1 – 2.2
0
Last Rack
2.3
Not Last Rack
Fault Action
2.4 – 2.6
Fault on communications loss
Hold last state on reset/program/test
Baud Rate
2.7 – 2.8
57.6K
Not Used
1.1 – 1.2
Not Used
Rack Address
1.3 – 1.8
2
Switch
Setting Description
3.1
0
1
Disable block transfer
Enable block transfer
3.2
0
1
Disable Logic Command/Status
Enable Logic Command/Status
3.3
0
1
Disable Reference/Feedback
Enable Reference/Feedback
3.4
0
1
Disable Datalink A (A1 and A2)
Enable Datalink A (A1 and A2)
3.5
0
1
Disable Datalink B (B1 and B2)
Enable Datalink B (B1 and B2)
3.6
0
1
Disable Datalink C (C1 and C2)
Enable Datalink C (C1 and C2)
3.7
0
1
Disable Datalink D (D1 and D2)
Enable Datalink D (D1 and D2)
3.8
0
1
Disable truncate last datalink
Enable truncate last datalink
2.1 – 2.2 2.2
1
0
1
0
2.1
1
1
0
0
Starting group 0
Starting group 2
Starting group 4
Starting group 6
2.3
0
1
Not last rack
Last rack with this address
2.4
0
1
Hold last state
Zero data
2.5
0
1
No fault. Use action of switch 2.4
Fault drive on communications loss
2.6
0
1
No fault. Use action of switch 2.4
Fault drive on Reset/Program/Test
2.7 – 2.8 2.8
0
0
1
2.7
0
1
0
57.6 kbps
115.2 kbps
230.4 kbps
1.1 – 1.2
Not Used
1.3 – 1.8 Varies
See “Setting the Rack Address” on
page 2-13
Off = 0
On = 1
Off = 0
On = 1
Off = 0
On = 1