6.12. Overload Object —CLASS CODE 0x002C
No class attributes are supported for the Overload Object. A single instance
(instance 1) of the Overload Object is supported:
The following common services are implemented for the Overload Object:
DeviceNet Interface Object — CLASS CODE 0x00B4
The following class attributes are supported for the DeviceNet Interface
Object:
Table B.39 Overload Object Instance Attributes
Attribute ID
Access Rule Name
Data Type
Value
7
Get
% Thermal Utilized
USINT
xxx% FLA
108
Get
Average %FLA
UINT
0…1000 %FLA
109
Get
% Thermal Utilized
USINT
0…100%
127
Get/Set
Single/Three Phase
BOOL
0=Single Phase
1=Three Phase
132
Get/Set
OL Warn Level
USINT
0…100% TCU
141
Get/Set
Jam Inhibit Time
USINT
0…250 Sec.
142
Get/Set
Jam Trip Delay
USINT
0.5…25.0 Sec.
143
Get/Set
Jam Trip Level
UINT
150…600 %FLA
144
Get/Set
Jam Warn Level
UINT
100…600 %FLA
145
Get/Set
UL Inhibit Time
USINT
0…250 Sec.
148
Get/Set
UL Warn Level
USINT
30…100 %FLA
Table B.40 Overload Object Common Services
Service
Code
Implemented for:
Service Name
Class
Instance
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Table B.41 DeviceNet Interface Object Class Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision