Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual
Page 59

Publication 193-UM006A-EN-P – October 2005
DeviceNet Information B-7
Connection Object — CLASS CODE 0x0005
No class attributes are supported for the Connection Object. Multiple
instances of the Connection Object are supported, instances 2 and 4 from the
group 2 predefined master/slave connection set, and instances 5-7 are
available explicit UCMM connections.
Instance 2 is the Polled I/O Message Connection. The following instance 2
attributes are supported:
Table B.19 Connection Object Instance 2 Attributes
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
State
USINT
0=Nonexistant
1= Configuring
3=Established
4=Timed out
2
Get
Instance Type
USINT
1=I/O Connection
3
Get
Transport Class Trigger
USINT
0x82: Server, Transport Class 2
(If alloc_choice!=polled and ack suppression
is enabled, the value = 0x80)
4
Get
Produced Connection ID
UINT
01111xxxxxx
xxxxxx=node address
5
Get
Consumed Connection ID
UINT
10xxxxxx101
xxxxxx=node address
6
Get
Initial Comm Characteristics
USINT
0x21
7
Get
Produced Connection Size
UINT
0…8
8
Get
Consumed Connection Size
UINT
0…8
9
Get/Set
Expected Packet Rate
UINT
in milliseconds
12
Get/Set
Watchdog Action
USINT
0=Transition to timed out
1=Auto deleted
2=Auto reset
13
Get
Produced Connection Path Length
UINT
8
14
Get/Set
Produced Connection Path
21 04 00 25 (assy inst) 00 30 03
15
Get
Consumed Connection Path Length
UINT
8
16
Get/Set
Consumed Connection Path
21 04 00 25 (assy inst) 00 30 03