A-2 Specifications

Recommended Control Circuit Fuse

KTK-R-6
(6 A, 600V)

Rated Number of Operations
Out A:
W/100-C-09…100-C43
W/100-C-60…100-C85
W/NEMA Size 0…2
W/NEMA Size 3

5,000,000
2,500,000
1,000,000
300,000

Input Ratings:

Terminals
IN 1:
IN 2:
SSV (Sensor Supply Voltage)

1
2
3

Supply Voltage (provided by module)

24V DC±15%

Type of Inputs

Current Sinking

ON-State Voltage

15V DC

On-State Current (turn-on)

2 mA

Steady State Current

5 mA

Off-State Voltage

5V DC

Off-State Current

0.5 mA

Transition Voltage

5…15V DC

Transition Current

0.5…2.0 mA

Environmental Ratings:

Ambient Temperature Tamb
Storage
Operating
(Open)
(Enclosed)

-40…+85°C (-40…+185°F)

-20…+60°C (-4…+140°F)
-20…+40°C (-4…+104°F)

Humidity
Operating
Damp Heat - Steady State
Damp Heat - Cyclic

5…95% non-condensing
per IEC 68-2-3
per IEC 68-2-30

Cooling Method

Natural Convection

Vibration (per IEC 68-2-6)

3 G

Shock (per IEC 68-2-27)

30 G

Maximum Altitude

2000 m

Pollution Environment

Pollution Degree 2

Terminal Marking

EN 50012

Degree of Protection

IP20

Electromagnetic Compatibility

Electrostatic Discharge Immunity
Test Level

Performance Criteria

8 kV Air Discharge
4 kV Contact Discharge
1①✍