Parameter group listing, Monitor group – Rockwell Automation 193-EDN E1Plus Overload Relays - DeviceNet Module User Manual
Page 26
Publication 193-UM006A-EN-P – October 2005
4-2 Device Parameters
Parameter Group Listing
The 193-EDN DeviceNet Module contains six parameter groups
Monitor Group
Table 4.1 Parameter Groups
Monitor
parameters
Advanced Setup
Reset/Lock
DeviceNet Setup
I/O Setup
Trip History
1 Average %FLA
12 Trip Enable
14 Trip Reset
26 AutoBaudEnable
34 OutA Pr FltState
5 Trip Log 0
2%Therm Utilized
13 Warning Enable
24 Program Lock
27 NonVol Baud Rate
35 OutA Pr FltValue
6 Trip Log 1
3 Trip Status
15 Single/Three Ph
25 Set to Defaults
28 Output Assembly
36 OutA DN FltState
7 Trip Log 2
4 Warning Status
16 OL Reset Mode
29 Input Assembly
37 OutA DN FltValue 8 Trip Log 3
10 Device Status
17 OL Warning Level
30 Prod Assy Word 0
38 OutA DN IdlState
9 Trip Log 4
11 Firmware
18 Jam Inhibit Time
31 Prod Assy Word 1
39 OutA DN IdlValue
19 Jam Trip Delay
32 Prod Assy Word 2
40 IN1 Assignment
20 Jam Trip Level
33 Prod Assy Word 3
41 IN2 Assignment
21 Jam Warn Level
22 UL Inhibit Time
23 UL Warn Level
Average %FLA
Parameter No. 1
This parameter reports the average motor current.
The value is reported as a percentage of motor rated
current (dial setting on the E1 Plus Overload Relay),
and is reported in increments of 5.
Access Rule
Get
Data Type
UINT
Group
Monitor
Units
%FLA
Min. Value
0
Max. Value
1275
Default Value
None
% Therm Utilized
Parameter No. 2
This parameter reports the percent thermal
utilization of the connected motor.
Access Rule
Get
Data Type
USINT
Group
Monitor
Units
%
Min. Value
0
Max. Value
100
Default Value
None