Appendix a, Sccr ratings, Appendix – Rockwell Automation 150 SMC Quick Start Manual User Manual
Page 55

Rockwell Automation Publication 150-QS003D-EN-P - November 2013
53
Appendix
A
SCCR Ratings
SCCR Ratings
Table 26 - SCCR (High Capacity Fault) Electrical Ratings
Type 1 Coordination
➊
SCPD Performance
➋
Class J or Class L Fuse
➌
Inverse Time (Thermal Magnetic) Circuit Breaker
➍
SCCR List
(High Capacity Fault)
Maximum
Available
Fault (600V) [kA]
Amps
480V, 65kA Maximum
Typical
Max.
Bul. 140U
Frame Size
➎
Max.
Amps
Cat. No.
➎
Rating Plug
Line Device
Operational
Current Rating
[A]
90
100
150
200
M
350
140U-M6D3-D35
not required
110
175
225
300
140U-M6D3-D30
not required
140
225
300
400
140U-M6D3-D40
not required
180
300
400
400
140U-M6D3-D40
not required
210
350
450
M
600
140U-M6D3-D60
not required
260
450
500
700
140U-M6D3-D70
not required
320
500
700
800
140U-M6D3-D80
not required
361
601
800
N
1000
140U-N6L3-E12
140U-NRP3-E10
420
700
800
1200
140U-N6L3-E12
140U-NRP3-E12
520
800
1000
1200
140U-N6L3-E12
140U-NRP3-E12
Delta Device
Operational
Current Rating
[A]
155 65
250
300
M
450
140U-M6D3-D45
not required
190
300
400
500
140U-M6D3-D50
not required
242
400
500
700
140U-M6D3-D70
not required
311
500
600
700
140U-M6D3-D70
not required
363
601
800
N
1000
140U-N6L3-E12
140U-NRP3-E10
450
700
1000
1200
140U-N6L3-E12
140U-NRP3-E12
554
800
1200
1200
140U-N6L3-E12
140U-NRP3-E12
625
1000
1200
R
1600
140U-R6L3-E20
140U-R20RP3-E16
727
1200
1600
2000
140U-R6L3-E20
140U-R20RP3-E20
900
1200
2000
2000
140U-R6L3-E20
140U-R20RP3-E20
➊
Basic Requirements for Type 1 Coordination: Under the short-circuit condition, the starter shall cause no danger to persons or the installation. The
starter may not be suitable for further service without repair or replacement of parts. For further details, See UL508/CSA C22.2 No. 14 and EN 60947-4-2.
➋
Consult local codes for proper sizing of short-circuit protection.
➌
High capacity fault ratings when used with a time delay Class J fuse or time delay Class L fuse.
➍
Circuit Breaker must be of the designated 140U Frame
➎
Other circuit breakers pending.