Appendix a, Sccr ratings, Appendix – Rockwell Automation 150 SMC Quick Start Manual User Manual

Page 55

background image

Rockwell Automation Publication 150-QS003D-EN-P - November 2013

53

Appendix

A

SCCR Ratings

SCCR Ratings

Table 26 - SCCR (High Capacity Fault) Electrical Ratings

Type 1 Coordination

SCPD Performance

Class J or Class L Fuse

Inverse Time (Thermal Magnetic) Circuit Breaker

SCCR List
(High Capacity Fault)

Maximum
Available
Fault (600V) [kA]

Amps

480V, 65kA Maximum

Typical

Max.

Bul. 140U
Frame Size

Max.
Amps

Cat. No.

Rating Plug

Line Device

Operational

Current Rating

[A]

90

100

150

200

M

350

140U-M6D3-D35

not required

110

175

225

300

140U-M6D3-D30

not required

140

225

300

400

140U-M6D3-D40

not required

180

300

400

400

140U-M6D3-D40

not required

210

350

450

M

600

140U-M6D3-D60

not required

260

450

500

700

140U-M6D3-D70

not required

320

500

700

800

140U-M6D3-D80

not required

361

601

800

N

1000

140U-N6L3-E12

140U-NRP3-E10

420

700

800

1200

140U-N6L3-E12

140U-NRP3-E12

520

800

1000

1200

140U-N6L3-E12

140U-NRP3-E12

Delta Device

Operational

Current Rating

[A]

155 65

250

300

M

450

140U-M6D3-D45

not required

190

300

400

500

140U-M6D3-D50

not required

242

400

500

700

140U-M6D3-D70

not required

311

500

600

700

140U-M6D3-D70

not required

363

601

800

N

1000

140U-N6L3-E12

140U-NRP3-E10

450

700

1000

1200

140U-N6L3-E12

140U-NRP3-E12

554

800

1200

1200

140U-N6L3-E12

140U-NRP3-E12

625

1000

1200

R

1600

140U-R6L3-E20

140U-R20RP3-E16

727

1200

1600

2000

140U-R6L3-E20

140U-R20RP3-E20

900

1200

2000

2000

140U-R6L3-E20

140U-R20RP3-E20

Basic Requirements for Type 1 Coordination: Under the short-circuit condition, the starter shall cause no danger to persons or the installation. The

starter may not be suitable for further service without repair or replacement of parts. For further details, See UL508/CSA C22.2 No. 14 and EN 60947-4-2.

Consult local codes for proper sizing of short-circuit protection.

High capacity fault ratings when used with a time delay Class J fuse or time delay Class L fuse.

Circuit Breaker must be of the designated 140U Frame

Other circuit breakers pending.