Rockwell Automation Publication 150-QS003D-EN-P - November 2013

Chapter 3 Programming

Table 12 - Rotary Switch Position Settings & Resulting Values — Motor FLC
Configurations

S5 = Motor Full Load Current (FLC) Configuration — Controller Parameter 78

Position Setting

FLC

➊➋

[% of controller’s max]

Position Setting

FLC

➊➋

[% of controller’s max]

0

40 (default)

8

72

1

44

9

76

2

48

A

80

3

52

B

84

4

56

C

88

5

60

D

92

6

64

E

96

7

68

F

100

Since a set of switches do not provide the resolution to enter all possible FLC combinations like a keypad,

switch S5 allows you to configure the motor’s FLC in the SMC-50 by using a percentage (%) of the controller’s
rated FLC (e.g., 90 A, 110 A, 180 A, etc.).

To determine the S5 switch setting for an inside-the-delta motor configuration, use the following equations:

NOTE:

1 If the calculated value does not match a switch position, use the previous
(lower percentage) switch setting.

2 The inside-the-delta motor configuration can be selected using Parameter 44
(Motor Connection) or automatically during a controller tuning process. The
tuning process is done during the initial system start after changing any of the
tuning parameters and initializing a start or by pressing and holding the SMC-50
reset push button for at least 10 seconds with the motor stopped and then
initializing a start.

For a 60 A motor and a 90 A controller:

% of controller’s max FLC for a 60 A motor = 64% of 90 A (57.6 A), or Switch Position 6

EXAMPLE

Step 1

Motor Nameplate FLC

1.73

= X

x 100 =

Step 2

X

SMC-50 Controller Rating

S5 Switch Setting

Step 1

100 A

1.73

= 57.8 A

Step 2

57.8 A

90 A

x 100 = 64%

EXAMPLE

Result From the result of 64%, the S5 switch setting is position 6.