Rockwell Automation 150 SMC Quick Start Manual User Manual
Page 25
Rockwell Automation Publication 150-QS003D-EN-P - November 2013
23
Installation Chapter 2
Optional Cat. No. 150-SM6 Parameter Configuration Module
(PCM)
The Cat. No. 150-SM6 PCM provides simple and limited configuration of the
SMC-50. This PCM can be inserted into any control module option port (7, 8,
or 9). Only one PCM is allowed per control module.
Parameters that are configured by the PCM will appear as read-write parameters
to other configuration devices whose values represent the switch settings. The
parameter values set by the PCM are stored in the control module memory.
Parameters that are not defined and therefore are not configurable by the
150-SM6 PCM can be configured through other means (e.g., Human Interface
Module (HIM), Connected Components Workbench (CCW), DriveExplorer
or DriveExecutive software), if necessary.
Additional information regarding parameter configuration using a PCM is in
150-SM3
Optional outputs:
Terminals B1…B4
Number of Outputs
2 Single-ended
Normal Operating Output Ranges
±10V, 0…10V, 0…5V, 0…20 mA, 4…20 mA
Full Scale Operating Output Ranges
±10.5V, 0…10.5V, -0.5…5.25V, 0…21 mA, 3.5…21 mA
Output Resolution
±10.5V, 0 …10.5V, -0.5…5.25V,
0.5…5.25V, 0…21 mA, 3.5 …21 mA
16 bit (15 plus sign bipolar)
Resistive Load on Current Output
0…750
Ω
Load Range on Voltage Output
1 k
Ω at 10V DC
Max. Inductive Load (Current Outputs)
15 mH
Max. Capacitive Load (Voltage Outputs)
100
μF
Overall Accuracy
Voltage Terminal: ±0.5% full scale at 25° C
Current Terminal: ±0.35% full scale at 25° C
Accuracy Drift with Temperature
±5 PPM / ° C
Output Impedance
15
Ω (typical)
Open and Short-Circuit Protection
Yes
Maximum Short-Circuit Current
45 mA
Output Overvoltage Protection
Yes
Control Circuit
Specification