beautypg.com

Rockwell Automation 150 SMC Quick Start Manual User Manual

Page 25

background image

Rockwell Automation Publication 150-QS003D-EN-P - November 2013

23

Installation Chapter 2

Optional Cat. No. 150-SM6 Parameter Configuration Module
(PCM)

The Cat. No. 150-SM6 PCM provides simple and limited configuration of the
SMC-50. This PCM can be inserted into any control module option port (7, 8,
or 9). Only one PCM is allowed per control module.

Parameters that are configured by the PCM will appear as read-write parameters
to other configuration devices whose values represent the switch settings. The
parameter values set by the PCM are stored in the control module memory.

Parameters that are not defined and therefore are not configurable by the
150-SM6 PCM can be configured through other means (e.g., Human Interface
Module (HIM), Connected Components Workbench (CCW), DriveExplorer
or DriveExecutive software), if necessary.

Additional information regarding parameter configuration using a PCM is in

Chapter 3

.

150-SM3
Optional outputs:
Terminals B1…B4

Number of Outputs

2 Single-ended

Normal Operating Output Ranges

±10V, 0…10V, 0…5V, 0…20 mA, 4…20 mA

Full Scale Operating Output Ranges

±10.5V, 0…10.5V, -0.5…5.25V, 0…21 mA, 3.5…21 mA

Output Resolution
±10.5V, 0 …10.5V, -0.5…5.25V,
0.5…5.25V, 0…21 mA, 3.5 …21 mA

16 bit (15 plus sign bipolar)

Resistive Load on Current Output

0…750

Ω

Load Range on Voltage Output

1 k

Ω at 10V DC

Max. Inductive Load (Current Outputs)

15 mH

Max. Capacitive Load (Voltage Outputs)

100

μF

Overall Accuracy

Voltage Terminal: ±0.5% full scale at 25° C
Current Terminal: ±0.35% full scale at 25° C

Accuracy Drift with Temperature

±5 PPM / ° C

Output Impedance

15

Ω (typical)

Open and Short-Circuit Protection

Yes

Maximum Short-Circuit Current

45 mA

Output Overvoltage Protection

Yes

Control Circuit

Specification