Chapter 3 Programming

Quick Setup

Access the basic programming configuration group in the Setup category. This
group provides a limited parameter set, allowing quick startup with minimal
adjustments.

Table 19 - Quick Start Parameters

Parameter
Number

Parameter
Name Description/Function

Value(s)

Default

46

Line Voltage

Enter the system 3-phase line voltage value. A value must be entered for the
voltage protection functions to work properly.

0…700V

480

47

Rated Torque

Use for Torque Ramp Rating Starting Mode. Enter the maximum motor rated in
Newton meters.

1…1000 N•m

10

48

Rated Speed

Use for Torque Ramp Rating Starting Mode. Enter the rated speed of the motor.

750, 900, 1500, 1800,
3500, 3600 RPM

1800

49

Starting Mode

Enter the desired starting mode for the application.
Related Parameters for the Starting Mode:
Full Voltage:
None
Current Limit: Current Limit Level, Ramp Time, Kickstart Time, Kickstart Level
Soft Start: Initial Torque, Ramp Time, Current Limit, Kickstart Time, Kickstart Level
Linear Speed: Initial Torque, Ramp Time, Current Limit
Torque Ramp: Starting Torque, Maximum Torque, Ramp Time, Current Limit,
Kickstart Time, Kickstart Level
Pump Start: Initial Torque, Ramp Time

Full Voltage, Current Limit, Soft
Start, Linear Speed, Torque
Ramp,
Pump Start

Soft Start

50

Ramp Time

Enter the amount of time desired for the motor starting ramp to take.

0.0 - 1000 seconds

10

51

Initial Torque

Motor torque level at which the start ramp begins.

0...90%LRT

70

52

Maximum
Torque

Use the Torque Ramp Starting mode. Enter the maximum motor torque at the end
of the start ramp required for the application.

0…300%

250

53

Current Limit
Level

Enter the value of the maximum current allowed during the ramp time.

50-600% FLC

350

56

Input 1

Allows the selection of how input 1 (CM terminal #11) effects the function of the
SMC-50 controller.

Disable, Start, Coast,
Stop Option, Start/Coast,
Start/Stop, Slow Speed,
Dual Ramp, OL Select,
Fault, Fault NC, Clear Fault,
Emergency Run,
Motor Heater

Start/Coast

57

Input 2

Allows the selection of how input 2 (CM terminal #10) effects the function of the
SMC-50 controller.

Disable

65

Stop Mode

Enter the desired stopping mode for the application.
Related Parameters to the Stopping Mode:
Coast: None Soft Stop: Stop Time Linear Speed: Stop Time, Current Limit
Pump Stop: Stop Time SMB: Braking Current Ext. Brake: Stop Time

Coast, Soft Stop,
Linear Speed, Pump Stop,
SMB,
Ext. Brake

Coast

66

Stop Time

Defines the time desired to ramp form run to stop for a specific stop mode. For Ext
Brake mode, the Stop Time = the time the Aux contact is closed to energize an
external brake.

0…999 seconds

0

75

Overload Class

Enter the desired motor overload trip class.

5…30

10

77

Service Factor

Enter the Service Factor of the motor.

0.01…1.99

1.15

78

Motor FLC

Enter the motor specified Full Load Current (FLC) value. This value must be entered
to ensure the controller can provide proper motor current (e.g. - Overload)
protection.

1.0…2200.0 A

1.0

172

Aux1
Configuration

Allows selection of the operation for Auxiliary relay output contact #1 (control
module terminals #4 and #5).

Normal, UTS, Fault, Alarm,
External Bypass, External
Brake, Auxiliary Control,
Network 1, Network 2,
Network 3, Network 4.

Normal

176

Aux 2
Configuration

Allows selection of the operation for Auxiliary relay output contact #1 (control
module terminals #6 and #7).

Normal

Normal = The contact is closed when the Start command is initiated and remains closed during a stop maneuver. After the stop is complete, the contact opens.