Chapter 4 Operation and Troubleshooting

2.

Press the "HOLD TO TEST / PUSH TO RESET" push button, located
on the front of the controller, for ten seconds with the motor stopped.
During the next start cycle, the tuning process will occur. The controller's
status LED will flash amber indicating that Tuning will occur on the next
start cycle.

3.

When the controller processes a "Load Factory Defaults" command via
Parameter Management, Parameter 229.

NOTE: If a motor that is smaller or larger than normal is used for initial system
test, a motor tuning cycle must be performed on the motor used in the final
installation.

Troubleshooting with
Diagnostic LEDs

Controller LED Status Indicator

The SMC-50 controller’s multi-color LED Status Indicator and HOLD TO
TEST, PUSH TO RESET button are located below the HIM bezel port. The
Status LED indicates the status and fault conditions of the SMC-50 controller.

Table 20 - Corresponding LED Color and Fault Conditions

The HOLD TO TEST, PUSH TO RESET button provides the ability to reset
an alarm/fault, test for a fault condition, and initiate the tuning mode.

Table 21 - Function Initiation of the HOLD TO TEST, PUSH TO RESET Button

Status LED Color

Device Mode

SMC Status

Green

Running

Running without an alarm

Green/Amber

Running

Running with an alarm

Green Flashing

Ready

Ready (no inhibit and no fault) without an alarm

Amber Flashing

Ready

Ready (no inhibit and no fault) with tuning
enabled on the next start

Amber

Ready

Ready with alarm (no tuning enabled)

Red/Amber

Inhibit

Inhibited; cannot start due to a Stop command

Red

Faulted

A non-resettable fault has occurred

Red Flashing

Faulted

A resettable fault has occurred

Red/Green

Download

Firmware is being downloaded

Function

Time Required to Press Button

Fault Reset

Momentary (less than 2 seconds)

Test Fault

Greater than 3 seconds, but less than 10 seconds

Initiate Tuning Mode

Greater than 10 seconds

The motor must be stopped.