Operation and Troubleshooting Chapter 4

Table 24 - SMC-50 Controller Fault Codes

Display Fault

HIM or
Software
Fault Code

Enabled

Possible Causes

Possible Solutions

Line Fault with
Phase Indication

1, 2, 3

Prestart
and
Running

Missing supply phase
Motor not connected properly
Incoming 3-phase voltage

instability

Check for open line (i.e. blown fuse)
Check for open load lead
Verify power quality

Shorted SCR
with Phase
Indication

4, 5, 6

All

Shorted power module

Check for shorted SCR, replace power module if necessary

Open Gate with
Phase Indication

7, 8, 9

Start or
Stop

Open gate circuitry

Loose gate lead

Perform resistance check; replace power module if

necessary

Check gate lead connections to the control module

PTC Power Pole
and SCR
Overtemp

10 or 60

Controller ventilation blocked
Controller duty cycle exceeded
Fan failure
Ambient temperature limit

exceeded

Failed thermistor

Check for proper ventilation
Check application duty cycle
Wait for motor to cool or provide external cooling
Replace power module or control module as needed

Replace fan

Motor PTC

59

Running

Motor ventilation blocked
Motor duty cycle exceeded
PTC open or shorted

Check for proper ventilation
Check application duty cycle
Wait for motor to cool or provide external cooling then check

resistance of PTC

No Load Fault

14, 15, 16, 17

Prestart
Only

Loss of load side power wiring

with phase indication (15=A, 17=C)

Start command cycled

unexpectedly with motor rotating

Check all load side power connections

Check motor windings

Voltage
Unbalance and/
or Current
Imbalance

18 and/or 42

Running

Supply unbalance is greater than

the user-programmed value

The delay time is too short for the

application

Check power system and correct if necessary, then correct

the user-programmed value

Extend the delay time to match the application requirements

Overvoltage

19

Running

Supply voltage is greater than the

user-programmed value

The delay time is too short for the

application

Check power system and correct if necessary, otherwise

correct the user-programmed value

Extend the delay time to match the application requirements

Undervoltage

20

Running

Supply voltage is less than the

user-programmed value

The delay time is too short for the

application

Check power system and correct if necessary, otherwise

correct the user-programmed value

Extend the delay time to match the application requirements

Overload

21

Running

Motor overloaded
Overload parameters are not

matched to the motor

Check motor overload condition
Check values for overload class and motor FLC and verify

current draw of the motor

Underload

22

Running

Broken motor shaft, belts, tool

bits, etc.

Pump cavitation
Incorrect user setting

Check pump system, machine drive components, and loading
Check settings
Repair or replace motor

Jam

23

Running

Motor current has exceeded the

user-programmed jam level

Correct source of jam or excessive loading and check

programmed time value

Stall

24

Running

Motor did not reach full speed by

the end of the programmed ramp
time

Incorrect user setting

Check pump system, machine drive components, and

loading. Repair or replace motor, if necessary.

Check settings

Phase Reversal

25

Prestart
only

Incoming supply voltage is not the

expected ABC sequence

Check power wiring and correct if necessary