Rockwell Automation Publication 150-QS003D-EN-P - November 2013

Chapter 2 Installation

PTC Thermistor Sensors

The 150-SM2 option module allows the SMC-50 to interface with motor PTC
sensors to monitor motor temperature. The following table defines the PTC
input and response ratings.

Table 8 - PTC Input & Response Ratings

Figure 17 - Combined Wiring Diagram of All Cat. No. 150-SM2 Sensors

Customer-supplied.

The 825-MCM can be used with or without an external bypass contactor. If an external bypass contactor is used

then the 825-MCM must be installed in order to use current-based motor protective features including the
motor overload feature. Cable length is 4 meters. Only the cable provided with the 825-MCM is compatible
with the 150-SM2.

The 825-CBCT core balance sensor mounts separately from the SMC-50 and must be placed within 3 meters of

the SMC-50. When connecting the 825-CBCT ground-fault sensor, the secondary of the CT must be shorted until
connection to the 150-SM2 module is complete.

See the user manual for additional bypass configurations (e.g., emergency run-off bypass) and application

considerations.

To meet product susceptibility requirements, a single ferrite core must be placed around any or all sensor (e.g.,

PTC, ground fault, etc.) wires connected to the 150-SM2 Option Module. The recommended core is a Fair-Rite
Products Corp Part Number 0431167281 or equivalent.

Ensure the 150-SM2 Turns Ratio, Parameter X.5, is configured to match the 825-CBCT Turns Ratio 100:1

(X.5=100).

Response Resistance

3400

Ω ±

150

Ω

Reset Resistance

1600

Ω

± 100

Ω

Short-Circuit Trip Resistance

25

Ω

± 10

Ω

Maximum Voltage at PTC Terminals

R

PTC

= 4 K

Ω

< 7.5V

R

PTC

= open

30V

Maximum Number of Sensors Connected in Series

6

Maximum Cold Resistance of PTC Sensor Chain

1500

Ω

Response Time

800 ms

RG25U

Female

TB4

TB4

TB3

TB3

TB2

TB2

150-SM2 Module Circuit Board

RG25U

Male

1

1

2

2

Shield

To Control

Module

Terminal #3

Ground

Shield

T1/2

T2/4

T3/6

L1/1

L2/3

L3/5

SMC-50

Fast-Acting SCR

Fuses (optional)

External Bypass

825-CBCT

Core Balance

Ground Fault

Sensor

Circuit

Branch

Protection

Motor PTC Sensor Cab

le

825-MCM Cable

825-MCM

Shield

White

Blac

k

M

1

1 2

1 2

1

1

1 4

1 3

5

6

1