Rockwell Automation Publication 150-QS003D-EN-P - November 2013

31

Installation Chapter 2

Figure 21 - Wiring Diagram for All Frames (Cat. No. 150-S…) with Bypass Contactor
and External Overload

Customer supplied.

Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance

is required on the motor. See the Isolation Contactor Applications for details.

Bypass must be controlled by an auxiliary contact of the SMC-50 that is configured for external bypass.

Bypass contactor must be fully rated to motor Hp/kW and FLA.

NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching

components allows uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To
prevent potential personal injury or equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting
the motor’s locked rotor current on the line side of the SMC-50 is recommended. Operation of the isolation device should be coordinated using one of
the SMC-50 auxiliary contacts configured to NORMAL.