beautypg.com

Monitoring dcs registers – Rockwell Automation 56AMXN/B ControlLogix AutoMax Comm Module User Manual

Page 55

background image

AutoMax DCSNet/RE RIO Module Page

55

Publication number 56AMXN-UM002A-EN-P November 2002

Monitoring DCS Registers

Select Monitor/DcsRegs to monitor the AutoMax DCS registers on any
drop.

Figure 17 DCS Register Display

Use the Drop listbox to select the drop number to display.

For drops 1-55, registers 0-31 contain the data from the slave to the
master. Registers 32-63 contain the data from the master to the slave.

WARNING! If you change values in the DCS registers, the values on
the module will change. Consider the consequences of changing data on
the DCS network.

You can use 56AmxnMon to change values in DCS registers. Before
you can do this, you must check Allow Edits. You will be asked to
confirm this. If you change values for data that is mapped into
ControlLogix scheduled data, the value you write will be overwritten
when the next scheduled data update occurs.

This manual is related to the following products: