Wire diagram - 55 series electric strike – SDC 55 SERIES ELECTRIC STRIKE User Manual

Page 3

background image

P:\INSTALLATION INST\ELECTRIC STRIKES\INST-55\INST-55.vsd REV D 10-12 Page 3

WIRE DIAGRAM - 55 SERIES ELECTRIC STRIKE

LCM

LBM

DBM

N/C (Powered = Open)

COM

Strike Input: Dual Voltage

600 mA @ 12VDC
300 mA @ 24VDC

Contacts: SPDT, Dry, 5 Amp @ 30V

N/C (Latched = Open)

COM

N/O (Latched = Closed)

N/C (Bolt Thrown = Open)
COM

N/O (Bolt Thrown = Closed)

ORG/BLK
WHT/BLK

YEL/BLK

ORG
WHT

YEL

ORG/RED
WHT/RED

YEL/RED

STRIKE

Red
Black

+

_

12V/600mA

24V/300mA

Power

Connector

12 or 24V

DC

Power Supply

Fail-Safe

Fail-Secure

+

-

ACCESS

CONTROL

+ RED

~

-

+

~

~

~

YEL

YEL

- WHT

12 or 24V

AC

Transformer

N/O (Powered = Closed)

AC to DC Rectifier

SDC BR64XL

*

*

NOTE:

Power wires must not be connected

to supply wires larger than 18AWG

YEL/BLK

WHT/BLK
ORG/BLK

ORG
WHT

YEL

COM

N/O
N/C

LCM

LMB

ORG/BLK
WHT/BLK

YEL/BLK

ORG
WHT

YEL

COM

N/O
N/C

LCM

LMB

HIGH SECURITY DOOR SECURE MONITORING: LCM & LBM Required
LCM & LBM wired in series indicates door is closed, latched and strike is deadlocked or door is open or unlocked

FAIL SAFE MODE – Door Secure or Unlocked Status

FAIL SECURE MODE – Door Secure or Unlocked Status

FIG. 1

NOTE:

LCM Contacts Reversed

When in Failsafe Mode

*

Monitoring

Connectors

Cable 1

Red
White

+

_

Cable 2

SDC 12/24V Pigtail P/N CA-55-4

MOV

Remove Cover

Failsecure
Shown

Failsafe

FIG. 3

HORIZONTAL ALIGNMENT ADJUSTMENT

3A-Nominal Alignment: Loosen mounting screws.
Shift strike body behind the faceplate horizontally.
Tighten mounting screws.

3B-Excessive Alignment Issues:

Remove shim filler bar from keeper.

3A

3B

FIG. 2

FIELD REVERSIBLE
FAILSAFE / FAILSECURE

Failsecure Mode: Factory supplied, Failsecure
Failsafe Mode: Remove cover, push solenoid toward

end of strike as shown below.