P:\INSTALLATION INST\Electromagnetic Locks\INST-1575-76\INST-1575-76U.vsd REV A 01-09 Page 2

WIRING DETAILS:

N/C

N/O

COM

YEL

GRN

ORG

COMMON

GOOD BOND

NO/POOR BOND

WIRE

COLOR

CONTACT

DESCRIPTION

BOND SENSOR (BAS) WIRING

To Properly
Fused DC Power
source

(-)

(+)

* ACCESS CONTROL(S)

1575-76 EMLOCK

BLU
BLK
BRN

RED

(+)

(-)

24VDC @225mA

To Properly
Fused DC Power
source

(-)

(+)

* ACCESS CONTROL(S)

1575-76 EMLOCK

BLU

BRN

BLK

RED

(+)

(-)

12VDC @450mA

24VDC CONFIGURATION

12VDC CONFIGURATION

4. Mount the Emlock with hardware provided (See pages 3 & 4).

5. Tighten all screws. Install anti-tamper plugs over socket head mounting screws.

6. Install 1/2” or 3/4” conduit. A conduit outlet box must be provided within 15" of the lock for wire connections.

7. Make all wire connections to a fused power source with the power off.

INSTALLATION (CONT.):

150
18
18
14
14
12

AMPS
0.25
0.50
0.75
1.00
1.50
2.00
2.50
3.00
3.50

25
18
18
18
18
18
18
18
16
16

50
18
18
18
18
16
16
14
14

75
18
18
16
16
14
14
12

100
18
18
16
16
14
12

200
18
16
14
12

250
16
16
14

300
16
14
12

400
14
12

500
12

1000

DISTANCE IN FEET FROM POWER SOURCE TO FARTHEST LOCKING DEVICE

Minimum Wire Gauge

For 12 Volts AC or DC

150
18
18
18
16
16
14
14
12

AMPS
0.25
0.50
0.75
1.00
1.50
2.00
2.50
3.00
3.50

25
18
18
18
18
18
18
18
18
18

50
18
18
18
18
18
18
18
16
16

75
18
18
18
18
18
18
16
14
14

100
18
18
18
18
16
16
14
14
12

200
18
18
16
16
14
14
12
12

250
18
18
16
14
12
12

300
18
16
16
14

400
18
16
14
12

500
16
14
12

1000
16

DISTANCE IN FEET FROM POWER SOURCE TO FARTHEST LOCKING DEVICE

Minimum Wire Gauge

For 24 Volts AC or DC

To determine the correct wire gauge to use on a single “circuit” the following information is required:

1. The quantity, voltage and current draw of all lock(s) to be connected to the circuit.
2. The distance in feet from the power supply to the furthest lock on the circuit.

Add together the current draw (amps) of all locks on the same circuit. Using the AWG Chart below, cross reference the total amps
with the distance between the power source and the furthest lock to determine the wire gauge required.

A single “circuit” describes a pair of wires run from the power supply to one or more locks that are wired in parallel. The distance from
the power supply to the furthest lock in the “circuit” must not exceed the distance number shown in the chart below and is based on
your selected wire gauge. If the distance shown in the chart is inadequate for your application, divide your locks up into 2 or more
separate “circuits” and use the chart to check each circuit independently. Fewer locks on each circuit may allow you to use a smaller
gauge wire or will allow you to increase the maximum distance between the power supply and the furthest lock on the circuit. More
than one circuit can be connected on the same power supply as long as the combined current required from all connected circuits
does not exceed the power supply rating.

NOTE: All wiring must be installed in accordance with all state and local codes.

N/C

N/O

COM

WHT

GRY

VIO

COMMON

ACTIVATE WHEN DOOR

OPEN

ACTIVATE WHEN DOOR

CLOSED

WIRE

COLOR

CONTACT

DESCRIPTION

DOOR POSITION SENSOR (DPS) WIRING

This manual is related to the following products: