Step 6 – SDC E1200 SERIES MAGNETIC LOCK User Manual

Page 3

background image

P:\INSTALLATION INST\Electromagnetic Locks\EXCEL\INST-E1200.vsd REV A 07-10 Page 3

6. Holding the magnet housing at each end, engage the entire length of the interlock detail, by pushing towards the
door. Tap with a soft hammer to ensure proper alignment and engagement.

CAUTION: The lock body must be held in place until secured with mounting screws. Secure socket head
screws provided inside the housing at each end. Start screws into threads carefully to avoid stripping the
threads. Check alignment and tighten screws. Pull wires through frame, mounting plate and magnet housing

STEP 6

7. Select jumper position for 12VDC or 24VDC. Connect power to magnetic lock.

A/C

MAINS

POWER

SUPPLY

12VDC

or

24VDC

SWITCH or

ACCESS

CONTROL

+

-

8. Test operation. When all is operating properly, tighten
all screws as shown. Install security pins and screws
as shown. Install anti-tamper plugs over socket head
screws using a soft hammer to avoid damage to the housing.

ATTACH THE RED SIDE OF THE CONNECTOR HERE

FOR A GREEN LED ENERGIZED & SECURE (RED=ENERGIZED & UNSECURE)

ATTACH THE GREEN SIDE OF THE CONNECTOR HERE

FOR A RED LED ENERGIZED AND UNSECURE (GREEN=ENERGIZED & SECURE)

COM

NC

NO

Door Position Sensor (Reed switch)

RED (open with door closed)

GREEN (closed with door closed)

BLACK

R

G

B

W

G

B

R

Door
Position
Sensor

Lock
Status
Switch
(Relay)

Power

Supply

Voltage Jumper

8

N

C

7

C

6

N

O

5

N

C

4

C

3

N

O

2

-

1

+

12VDC

24VDC

LED

RED

GRN