P:\INSTALLATION INST\Electrified Lockset\INST-Z7500.vsd REV E 01-13 Page 2

Wiring assignments for the optional SC-10 cable with socket connectors are the same.

VOLTAGE

RESISTANCE IN

OHMS 5%

+-

AMPS

24VDC

54.5

.44

24VAC

13.6

.45

115VAC

293

.20

Important Note: Because of design, field OHM tests of AC
solenoids may produce erratic readings and cannot be
used to determine the solenoids condition.

The 7500 Series is a (PL) Electric Power to Lock Unit which is failsafe in that it unlocks when power is removed. The most commonly used function is
the 7540 and 7550 models which are locked when energized on the outside and free on the inside egress. Models 7510, 7520 & 7530 lock on both
sides when energized.

(1) Power on controller plunger does not throw.

1A Insufficient voltage

1A Check voltage with a meter at the lock

farthest from source with all locks energized.
Meter should indicate the same voltage
stamped on the solenoid body. If voltage is
low, either too small of a wire gauge was
used or there is too great of a load on the
line.

7510

Mortise lock is unlocked by
means of a remote switch.
Suggested: storerooms, records,
utility, tool cribs, man trap.

FUNCTIONS

7530

Mortise lock is unlocked by
a remote switch or by means of
a key from either side.
Suggested: communicating locks, man
trap

7550

Mortise lock is unlocked by
remote switch or by means of
an outside key or by rotating the
inside lever.
Suggested: stairtower doors, classrooms,
laboratories, offices, man trap.

7520

Mortise lock is unlocked by
remote switch or by means of
an outside key.
Suggested: storerooms, records,
utility, tool cribs, man trap.

7540

Mortise lock is unlocked by
a remote switch or by rotating
the inside lever which retracts
the mortise latch bolt and the
auxiliary latch.
Suggested: stairtower doors, control
centers, vaults, man trap.

1B Binding caused by uneven

plunger adjustment.

1B Adjust plunger evenly.

1C Electric portion wired wrong.

1C Review wiring diagram on side of lock &

instruction sheet.

(2) Latch bolt throws only part way, lock

chatters or buzzes.

2A Door alignment does not

permit latch bolt to enter
strike

2A Proper alignment must be achieved by correctly

hanging the door in a properly installed frame.
Modifying the lock and strike will not remedy the
problem.
Modification will only void UL listing and
warranty.

+

-

COM

N/C

N/O

RED

WHT

BLU/BLK

YEL/BLK

ORG/BLK

Voltage and current rating stamped on solenoid
Ground screw is provided on 115 VAC locks

Indicates door open

Common

Indicates door latch

BLU/BLK

YEL

ORG

Indicates door unlocked

Common

Indicates door secure

Optional Latched & Deadlocked Status

SPDT 5 Amps @ 125VAC

Optional Latch Status Sensor

SPDT 5 Amps @ 125VAC

(3) Inside lever is locked, outside is free.

3A Incorrect handing

3A Remove mortise lock and reverse hand.

(4) Latch position switch does not signal

properly.

4A 9A adjustment is off.

4A Adjust sensor. See Step 1 of instructions.

TROUBLE SHOOTING HiTower 7500 SERIES

R

SOLUTIONS

CAUSE

PROBLEM