Function library "LenzeIo1000Drv"

Function blocks

L_io1000ParAiDc - Parameterise analog inputs

Outputs

Identifier/data type

Value/meaning

bDone

BOOL

TRUE Parameter setting completed successfully

dnState

DINT

Status of parameter setting

• When the function has been executed successfully, the value "0" is output.

1 Parameter setting started
0 Parameter setting completed successfully

-1003 byNodeAdr input is not in valid range
-1004 Wrong value at byAnalogModuleNo input
-1005 Wrong value at byNoOfChannels input
-2000 Error while executing the internal block for writing CAN indices
-2002 Wrong value at the dwHandle input
-2003 Wrong value at the byNodeAdr input
-2006 Writing of a wrong CAN index
-2007 Timeout while writing a CAN index of the I/O system
-2100 Error while writing a parameter of the I/O system
-2101 Output buffer is full