Transport, Installation and Connection
72
BA8230
The recommended guidelines for copper cable cross-sections guarantee a voltage
drop of <3 % up to conductor temperatures of 50 °C. The values stated apply to a
400 V supply at rated current for frame size 1 up to approx. 80 m and for frame sizes
2, 3 and 4 up to approx. 160 m.
The maximum permitted cable lengths for connecting 3-phase asynchronous motors
to the 8230 frequency inverter are stated in
Table 24
.
Max. permissable motor cable lengths of the 8230 frequency inverter
8230 frequency inverter
Type
Max. suitable motor cable lengths, 8230 frequency inverter
Unscreened cable NYY/NYM
1)
Screened cable NYCWY
1)
no circuit
2)
with motor
choke
2) 4)
with motor
filter
3)
U
N
=400 V
f
p
=3 kHz
with motor
filter
3)
U
N
=460 V
f
p
=3 kHz
No circuit
2)
with motor
choke
2
with motor
filter
3)
U
N
=400 V
f
p
=3 kHz
with motor
filter
3)
U
N
=460 V
f
p
=3 kHz
[m]
[m]
[m]
[m]
[m]
[m]
[m]
[m]
8231
300
400
400
300
250
350
300
200
150
5)
120
5)
200
5)
150
5)
8232
300
450
450
350
250
350
350
250
150
5)
120
5)
200
5)
150
5)
8233
300
450
450
350
250
350
350
250
150
5)
120
5)
200
5)
150
5)
8234
300
450
450
350
250
350
350
250
150
5)
120
5)
200
5)
150
5)
Table 24: Max. permitted motor cable lengths