Operation and Software
BA8230
117
A-Output 1 terminal 33
This parameter determines which control variable is to be output as an analog signal
at the monitor output (D/A output) terminal :33 (AA1). Digital resolution is 12 bit, the
range of values at the analog output is -10 V ... +10 V.
Privided that Scal. A-Output 1 = 100 % the following apply according to the selction
list:
- Output frequency
f = standard frequency
(The standard frequency as supplied is 100 Hz.
At an output frequency of 50 Hz the voltage output is
5 V. In the negative direction also the output voltage
is negative).
- Speed
Output:
frequency
rated
on
Speed
Speed
V
10
∗
eg. 5 V: Synchronous speed at 50 Hz.
In the negative direction also the output voltage is
negative.
- Motor current
Output 10 V, if the r.m.s. value of the fundamental wave of
the motor current is equal to the maximum maximum
controller current.
- Motor voltage
Output 10 V, if the r.m.s. value of the fundamental wave of
the motor voltage is equal to the rated mains voltage
.
- Torque
10 V with rated torque of the parameterized motor.
- Motor power
10 V with rated power of the parameterized motor.
- Link voltage
Output 10 V, if the link voltage is equal to the rectification
value of the rated mains voltage.
- Variable 1 = XIL
100 % torque-forming component of motor current
based on unit rated current.
As supplied:
Output frequency
Scaling, A-Output 1
This parameter serves to scale the D/A output at terminal :33. It represents the
reference value which produces a 10 V output.
Adjustment range:
0 ... 200 %
As supplied:
100 %