Operation and Software
118
BA8230
A-Output 2 terminal 35
This parameter determines which control variable is to be output as an analog value
at the monitor output (D/A output) terminal :35 (AA1). Digital resolution is 12 bit, the
range of values at the analog output is -10 V ... +10 V.
Privided that Scal. A-Output 2 = 100 % the following apply according to the selction
list:
- Output frequency
f = rated frequency
(The rated frequency as supplied is 100 Hz.
At an output frequency of 50 Hz the output voltage is
5 V. In the negative direction also the output voltage
becomes negative).
- Speed
Output:
frequency
rated
on
Speed
Speed
V
10
*
eg. 5 V: Synchronous speed at 50 Hz.
In the negative direction also the output voltage is
negative.
- Motor current
Output 10 V, if the r.m.s. value of the fundamental wave of
the motor current is equal to the maximum maximum
controller current.
- Motor voltage
Output 10 V, if the r.m.s. value of the fundamental wave of
the motor voltage is equal to the rated mains voltage
.
- Torque
10 V with rated torque of the parameterized motor.
- Motor power
10 V with rated power of the parameterized motor.
- Link voltage
Output 10 V, if the link voltage is equal to the rectification
value of the rated mains voltage.
- Variable 2 = XIM
100 % magnetising current based on the rated current
of the unit.
As supplied:
Motor current
Scaling A-Output 2
This parameter is used for scaling the D/A output at terminal :35. It represents the
reference value which produces a 10 V output.
Adjustment range:
0 ... 200 %
As supplied.
100 %