Lenze EDB9300UES User Manual
Page 116

Operation and Software
BA8230
111
RS422: Address
This parameter determines the unit address for the 8230 frequency inverter for
communication through the RS422 serial interface (with the PC).
Adjustment range:
0 ... 15
As supplied:
0
RS422: Baud rate
This parameter determines the transfer speed for serial communication through the
RS422 interface (PC).
Adjustment range:
2400 ... 19200 Baud
As supplied:
19200 Baud
Parameter set no.
This parameter indicates the currently active parameter set and allows switching to a
second parameter set through entry of a different numerical value. For this, Terminal:
Parameter Set Changeover must be disabled.
Two parameter sets can be selected.
Range:
1, 2
As supplied:
1
Copy target: Set accessible on level 2
Function for copying all settings used in the currently active parameter set to another
parameter set selected with its parameter no. or by a terminal
signal (D-Input 3 terminal :16).
This parameter set is accessible on level 2.
To copy a parameter set the parameter copy target is to be set to 2 and then the
function: Copy: Parameter is executed. The value of the copy target parameter is to
be set to match the target parameter set number and is automatically reset to zero
after copying.