Commissioning Report
146
BA8230
Parameter setting
Object-Nr.
Parameter
Default setting
Unit
Value
04=ANALOG I/O’s
3240
Main demand. 27/28
0...10V/0...20mA
................
3210
Max. main demand
100.00
%
................
3211
Min. main demand
0.00
%
................
3216
Zero range main
1)
0.5
%
................
3241
Add.demand 29/30
0...10V/0...20mA
................
3218
Max. add demand
100.00
%
................
3219
Min. add demand
0.00
%
................
321A
Zero range add. d.
1)
0.5
%
................
310E
Main + add demand
No
................
310A
4-20mA monitor
Trip
................
3F00
A-output 1:33
Output frequency
................
3F01
A-output 2:35
Motor current
................
3F30
Skaling A-output 1
100.00
%
................
3F31
Skaling A-output 2
100.00
%
................
05=DIGITAL I/O’s
3250
D-input 1:14
Motpot up
................
3251
D-input 2:15
Motpot down
................
3252
D-input 3:16
Jogging
................
3F05
D-Ausgang1 23/24
Speed = ref
................
310D
Invert:23/24
No
................
3223
Band speed = ref.
24.90
1/min
................
3222
Band speed = zero
2.93
1/min
................
3221
Reference speed
750.05
1/min
................
3224
Ref. Load current
100.00
%
................
06=RATINGS
2211
Inverter-Type
................
2222
Inverter currents
3)
Unit type dependent, not adjustable
2212
Mains voltage
400
V
................
2214
Type of load
squared torque
................
2215
Break type
-
3)
................
2281
Nom.motor power
-
4)
kW
................
2284
Nom.motor voltage
380
4)
V
................
2288
Nom.motor speed
1460
4)
1/min
................
2287
Nom.motor frequ.
50
4)
Hz
................
2289
Star Delta
Stern
4)
................
2283
Nom.motor current
-
4)
A
................
2285
cos phi
0.85
4)
................
22C7
Motortype
3)
-
3)
................
2286
Stall/Nom. torque
3.0
4)
................
2294
R-stator + R-cable
1)
0.1924
4)
Ohm
................
1)
Protection Level 1
3)
Unit type dependent
4)
Motor type dependent
Code:
Date
Comm. No.
Contac.
FB No.:
Commissioning report
8230 frequency inverter
Drive data
Check.
Serial.No.:
Sheet 6
Show/Hide Bookmarks